3.6.1 PowerCom King UPS cable Software - UPSMon-II
AC_Fail and Bat_Low - normally open (shorted to GND when active).
3.7 Exide/Deltec/Fiskars
3.7.1 Fiskars PowerRite Max / PowerRite Pro Cable
3.7.2 Fiskars PowerRite UPS Port Configuration Table
Pin # | Signal Type | Function |
1 | Basic Modem Mode; Input: RS232 high pulse 4 to 5 seconds wide | Remote UPS off: In presence of AC, Output will turn off for 15 seconds after conditionaldelay. In absence of AC, output is kept off until normal AC returns |
1 | Serial Data Mode; Input: RS232 data | RS232 serial communication input. 1200 baud, 8-bit, no parity, one stop bit, one start bit, Xon/Xoff |
2 | Basic Mode; Output: RS232 level high | AC Input failure |
2 | Serial Data Mode; Output: RS232 data | RS232 serial communication output. Same as input |
3 | Output: Open collector transistor ON, 50 mA. 40 VDC rating | AC Input failure |
4 | Signal Common | Signal Common |
5 | Output: Open collector transistor ON. SO mA. 40 VDC rating | Impending low battery |
6 | Input: RS232 level low (-12V) | Plug and Play software enable trigger |
7 | Input: Relay contact or RS232 level | Remote output OFF/ON: UPS total output can be kept off with low signal or closing relay contact |
8 | Output: 8 to 25 VDC, 5 W constant power (0.63 A max. @ 8V) | Auxiliary Control Power |
9 | Chassis | Connection to chassis |
3.8 Hewlett-Packard PowerWise
3.8.1 HP PowerWise L600/L900/L1250 interface pinout
Pin# | Signal Type | Function |
1 | RS-232 Earth Ground | Signal Common for all RS-232 port signals (earth ground referenced) |
2 | RS-232 Transmit Output | Serial communication mode - output signal line. |
3 | RS-232 Receive Input / Shutdown | Serial communication mode - input signal line. Contact Closure mode - shuts down UPS if signal is held high (RS-232 level) for 200 milliseconds while UPS is operating in battery mode. |
4 | AC Line Fail (normally closed) | Contact Closure mode - opened when AC line fails and UPS is operating in battery mode (breaks connection between Pin#4 and Pin#5). |
5 | Contact Closure Common / RS-232 Common | Signal Common for all Contact Closure group / RS-232 Signal Common line. |
7 | Low Battery (normally open) | Contact Closure mode - closed when remaining "on-battery runtime" drops below the under-defined time limit (makes connection between Pin#7 and Pin#5). |
9 | AC Line Fail (normally open) | Contact Closure mode - closed when in battery mode (makes connection between Pin#9 and Pin#5). |
3.8.2 HP PowerWise L600/L900/L1250 cable
Hewlett-Packard Part# - 201-471-09 , Software - HP PowerWise Assistant
3.9 Optiquest/Viewsonic
3.9.1 OptiUPS-650E/420E Cable
Optiquest Part# 730-02024-00 , Software - OPTI-SAFE+
3.10 Liebert
3.10.1 UPStation-GXT interface pinout
Pin# | Function |
1 | Low Battery (Optocoupler Collector: +V) |
2 | UPS TxD |
3 | UPS RxD |
4 | Remote ShutDown (+5..12VDC, 10 mA max); on battery operation |
5 | Common |
6 | Remote ShutDown (Short to pin 5); any mode operation |
7 | Low Batery (Optocoupler Emitter: -V) |
8 | Utility/Mains Fail (Optocoupler Emitter: -V) |
9 | Utility/Mains Fail (Optocoupler Collector: +V) |
Maximum voltage and current on pins 1,7,8,9 shall be 80 VDC, 10.0 mA max
3.10.2 UPStation-GXT dumb cable
Software - SiteNet Multilink.
3.11 Invertomatic-Victron (IMV)
3.11.1 Victron UPS "intelligent" (serial communication) cable
Victron Part# VIC-23/2 , Software - PowerFLAG
3.11.2 Victron UPS to modem serial connection cable
Victron Part# VIC-32
3.11.3 Victron contact closure (dumb) cable
Victron Part# VIC-25 (VIC-28) , Software - PowerFLAG
Кабель VIC-28 отличается от VIC-25 только отсутствием сигнала "Shutdown". Этот кабель также может быть использован для pаботы с WinNT UPS Service в конфигуpации: Power_Failure - Negative, Low_Battery - Negative, UPS_Shutdown - Positive.
3.11.4 Victron 19" UPS (RJ45) intelligent cable
Victron Part# VIC-45A , Software - PowerFLAG
3.11.5 Victron 19" SNMP-box (RJ45) to UPS cable
Victron Part# VIC-45 , Software - PowerFLAG